Tiêu chuẩn sản xuất:
IEC 62271-102
High-voltage switchgear and controlgear. Part 102 Alternat¬ing current disconnectors and earthing switches
IEC 62271-103
High-voltage switchgear and controlgear. Part 103: switches for rated voltage above 1 kV up to and including 52 kV
IEC 62271-1
High-voltage switchgear and controlgear-Part 1: common specifications
Thông số kỹ thuật
Insulation level |
|
|
NXB and NXBD |
NXA |
||||||
Rated voltage |
kV |
12 |
24 |
36 |
||||||
Power frequency withstand voltage, 50 Hz |
|
|
|
|||||||
– to earth and between phases |
kV |
28 |
50 |
70 |
||||||
– across the isolating distance |
kV |
32 |
60 |
80 |
||||||
Lightning impulse withstand voltage |
|
|
|
|||||||
– to earth and between phases |
kV |
75 |
125 |
170 |
||||||
– across the isolating distance |
kV |
85 |
145 |
195 |
||||||
Current ratings |
|
|
|
|||||||
Rated normal current |
A |
630 |
630 |
630 |
||||||
Mainly active load breaking current |
A |
630 |
630 |
630/400 |
||||||
Number of breaking operations CO |
n |
400 |
400 |
100/400 |
||||||
Line-charging breaking current |
A |
50 |
50 |
2 |
||||||
Cable-charging breaking current |
A |
50 |
50 |
40 |
||||||
Earth fault breaking current |
A |
50 |
50 |
130 |
||||||
Cable charging breaking current |
|
|
|
|||||||
under earth fault conditions |
A |
28 |
28 |
80 |
||||||
No-load transformer breaking current |
A |
|
|
20 |
||||||
Short-circuit ratings |
|
|
|
|||||||
Short-time withstand current, Ik |
kA/s |
20 kA/4 s |
20 kA/4 s |
12.5 kA/3 s |
||||||
Peak withstand current |
kA |
50 |
50 |
31.5 |
||||||
Short-circuit making current |
kA |
50 |
50 |
31.5 |
||||||
Number of making operations |
|
|
|
|||||||
– main switch 50 kA (CL E3) |
n |
5 |
5 |
|
||||||
– main switch 31.5 kA (CL E3) |
n |
10 |
10 |
5 |
||||||
– earthing switch 50 kA (CL E2) |
n |
3 |
3 |
|
||||||
– earthing switch 31.5 kA (CL E3) |
n |
5 |
5 |
|
||||||
Creepage distance |
mm |
620 |
620 |
1440 |
||||||
Ambient air temperature limits |
|
-40°C…+60°C*1 |
-40°C…+60°C*1 |
-40°C…+60°C |
||||||
Mechanical endurance (number of close-open operations) |
|
|
|
|||||||
– main switch |
n |
5000 |
5000 |
5000 |
||||||
– earthing switch*2 |
n |
2000 |
2000 |
|
||||||
Filling pressure (+20°C) |
bar (abs) |
1.4-1.5 |
1.4-1.5 |
1.8-1.9 |
||||||
Alarm pressure (+20°C) |
|
|
|
|||||||
– density switch |
bar (abs) |
1.2 |
1.2 |
1.65 |
||||||
– density gauge |
bar (abs) |
1.2 |
1.2 |
1.6 |
||||||
– low gas lock-out mechanism |
bar (abs) |
1.1 |
1.1 |
1.6 |
||||||
Weight |
|
|
|
|||||||
NXB (manual operated type) |
kg |
|
82 |
|
||||||
NXA (manual operated type) |
kg |
|
117 |
|
||||||
NXBD (manual operated type) |
kg |
|
138 |
|
||||||
Degree of protection of the mechanism box |
|
IP67 |
IP67 |
IP67 |
||||||